Corona-type partial discharge detection in power transformers using fiber bragg gratings
Subscribe/Renew Journal
We present a Fiber Bragg Grating (FBG) based scheme for sensing corona discharges in a power transformer. The corona-induced acoustic emissions detected using the FBG sensor pasted in a test cell is found to be correlated to the signals detected by HFCT sensor. A detailed spectral analysis of the detected signals is presented and the influence of electrode gap on the acoustic spectrum is investigated.
Keywords
Corona, partial discharge, power transformer, fiber bragg gratings 1.0