Open Access Open Access  Restricted Access Subscription Access
Open Access Open Access Open Access  Restricted Access Restricted Access Subscription Access

A Study of Electromagnetic Induction in HVDC Lines From Parallel AC Lines Under Short Circuit Conditions


Affiliations
1 Engineering Officer-2, High Power Laboratory, Central Power Research Institute, Bangalore - 560080, India
2 Joint Director, High Power Laboratory, Central Power Research Institute, Bangalore - 560080, India
     

   Subscribe/Renew Journal


High Voltage Direct Current (HVDC) lines running parallel to AC transmission lines will encounter electromagnetic induction which will rise to substantial levels during a short circuit. The actual magnitude of induced current depends on several factors like distance between the lines, soil resistivity etc. The unenergised DC line will also have a voltage due to induction and the associated discharging equipment will have to carry the induced current. This paper attempts to study the levels of induction encountered by the HVDC line and associated equipment during a short circuit in the AC line. It was observed that magnitude of induced current during steady state and three phase fault did not exceed 5 A while the magnitude of induced current during single phase to ground fault exceeded 15 A

Keywords

Double Circuit Transmission Lines, Electromagnetic Induction, HVDC, Short Circuit Currents
User
Subscription Login to verify subscription
Notifications
Font Size

Abstract Views: 217

PDF Views: 0




  • A Study of Electromagnetic Induction in HVDC Lines From Parallel AC Lines Under Short Circuit Conditions

Abstract Views: 217  |  PDF Views: 0

Authors

V. Sreeram
Engineering Officer-2, High Power Laboratory, Central Power Research Institute, Bangalore - 560080, India
S. Sudhakara Reddy
Joint Director, High Power Laboratory, Central Power Research Institute, Bangalore - 560080, India

Abstract


High Voltage Direct Current (HVDC) lines running parallel to AC transmission lines will encounter electromagnetic induction which will rise to substantial levels during a short circuit. The actual magnitude of induced current depends on several factors like distance between the lines, soil resistivity etc. The unenergised DC line will also have a voltage due to induction and the associated discharging equipment will have to carry the induced current. This paper attempts to study the levels of induction encountered by the HVDC line and associated equipment during a short circuit in the AC line. It was observed that magnitude of induced current during steady state and three phase fault did not exceed 5 A while the magnitude of induced current during single phase to ground fault exceeded 15 A

Keywords


Double Circuit Transmission Lines, Electromagnetic Induction, HVDC, Short Circuit Currents



DOI: https://doi.org/10.33686/prj.v12i2.189276