Open Access Open Access  Restricted Access Subscription Access

Studying Voltage Stability in Power System Considering Load Dynamics


Affiliations
1 Department of Electrical Engineering, Islamic Azad University, Takestan Branch, Takestan, Iran, Islamic Republic of
2 Electrical Engineering Department, Amirkabir University of Technology, Tehran, Iran, Islamic Republic of
 

This paper investigates on-load tap changer OLTC effect on voltage stability. Chaos theory used in this analysis is via the calculation of the maximum power transmission. Resulted chaotic behavior is exhibited by singular induced bifurcation which clearly shows the voltage stability of the power system with OLTC from a singular induced bifurcation point of view. The paper is organized as follows: 1) increasing in the maximum reactive power via increasing the ratio of OLTC and the possibility of voltage collapse decrease under the same load command. 2) Noting that the voltage instability is directly affected by the load characteristics, shown via the effect of OLTC on the voltage instability under different static load models. 3) Studying voltage stability in state space and the effects of the generator excitation current limit, the OLTC and load dynamics on voltage collapse. In addition, a small-disturbance voltage stability region of a power system is constructed. The voltage stability of the system is determined by the dynamic characteristics of both the OLTC and the load.

Keywords

On Load Tap Changer, Voltage Stability, State Space, Bifurcation Diagram
User

  • Taylor C W (1994). Power System Voltage Stability, Appendices:Voltage stability and the power flow problem, McGraw-Hill Ryerson, Limited, Technology & Engineering, 200–232.
  • Vaithianathan V R, Heinz S C et al. (1995). Dynamics of large constrainted nonlinear systems-a taxonomy theory, Proceedings of the IEEE, vol 83(11), 1530–1561.
  • Ohtsuki H, Yokoyama A et al. (1990). Reverse action of on-load tap changer in association with voltage collapse, IEEE Transactions on Power Systems, vol 6(1), 300–306.
  • Liu C, and Vu K T (1989). Analysis of tap-Changer dynamics and construction of voltage stability regions, IEEE Transactions on circuits and systems, vol 36(4), 575–590.
  • Zhu T X, Tso S K et al. (2000). An investigation into the OLTC effects on voltage collapse, IEEE Transactions Power Systems, vol 15(2), 515–521.
  • Kang P, and Birtwhistle D (2001). Condition monitoring of power transformer on-load tap-changers, Part 2: Detection of ageing from vibration signatures, IEE Proceedings - Generation Transmission and Distribu-tion, vol 148(4), 307–311.
  • Hong Y-Y and Yang Y-L (1998). Evaluation of control sequence for improving voltage stability in power systems, Electric Power Systems Research, vol 47(3), 205–213.
  • Rivas E, Burgos J C et al. (2009). Condition assessment of power OLTC by vibration analysis using wavelet transform, IEEE Transactions on Power Delivery, vol 24(2), 687–694.
  • Rivas E, Burgos J C et al. (2010). Vibration analysis using envelope wavelet for detecting faults in the OLTC tap selector, IEEE Transactions on Power Delivery, vol 25(3), 1629–1636.
  • Liu C C, and Vu K T (1989). Analysis of tap-changer dynamics and construction of voltage stability regions, IEEE Transactions on Circuits and Systems, vol 36(4), 575–590.
  • Vu K T, and Liu C C (1992). Shrinking stability regions and voltage collapse in power systems, IEEE Transactions on Circuits and Systems, vol 39(4), 271–289.
  • Vu K T, and Liu C C (1990). Dynamic mechanisms of voltage collapse, Systems and Control Letters, vol 15, 329–338.
  • Vancutsem T (1988). Dynamic and static aspects of voltage collapse, Proc. Engineering Foundation Conf. on Bulk Power System Voltage Phenomena: Voltage Security and Stability, Potosi (USA), 6.55–6.79.
  • Ohtsuki H, Yokoyama A et al. (1991). Reverse action or on-load tap changer in association with voltage collapse, IEEE Transactions on Power Systems, vol 6(1), 300–306.
  • Hill D J (1993). Nonlinear dynamic load models with recovery for voltage stability studies, IEEE Transactions on Power System, vol 8(1), 166–176.
  • Xu W, and Mansour Y (1994). Voltage stability analysis using generic dynamic load models, IEEE Transactions on Power System, vol 9(1), 479–493.

Abstract Views: 420

PDF Views: 0




  • Studying Voltage Stability in Power System Considering Load Dynamics

Abstract Views: 420  |  PDF Views: 0

Authors

H. Radmanesh
Department of Electrical Engineering, Islamic Azad University, Takestan Branch, Takestan, Iran, Islamic Republic of
S. S. Heidari Yazdi
Electrical Engineering Department, Amirkabir University of Technology, Tehran, Iran, Islamic Republic of
S. U. Mosazadeh
Electrical Engineering Department, Amirkabir University of Technology, Tehran, Iran, Islamic Republic of
G. B. Gharehpetian
Electrical Engineering Department, Amirkabir University of Technology, Tehran, Iran, Islamic Republic of

Abstract


This paper investigates on-load tap changer OLTC effect on voltage stability. Chaos theory used in this analysis is via the calculation of the maximum power transmission. Resulted chaotic behavior is exhibited by singular induced bifurcation which clearly shows the voltage stability of the power system with OLTC from a singular induced bifurcation point of view. The paper is organized as follows: 1) increasing in the maximum reactive power via increasing the ratio of OLTC and the possibility of voltage collapse decrease under the same load command. 2) Noting that the voltage instability is directly affected by the load characteristics, shown via the effect of OLTC on the voltage instability under different static load models. 3) Studying voltage stability in state space and the effects of the generator excitation current limit, the OLTC and load dynamics on voltage collapse. In addition, a small-disturbance voltage stability region of a power system is constructed. The voltage stability of the system is determined by the dynamic characteristics of both the OLTC and the load.

Keywords


On Load Tap Changer, Voltage Stability, State Space, Bifurcation Diagram

References